Adverse Currents in Simple Closed Networks
Electrical and Control Technologies 2011: Proceedings of the 6th International Conference on Electrical and Control Technologies (ECT-2011) 2011
Josifs Survilo, Edīte Bieļa-Dailidoviča

In non-uniform two-terminal lines, circulating and equalizing currents appear, in non-uniform rings – circulating current; these adverse currents cause extra power losses. Those losses are equal to the product of summary resistance and squared said currents and are independent of their direction. Equalizing current causes considerable losses by phase discrepancy of terminal voltages even when voltage magnitudes are equal. Equalizing current losses do not exceed ¼ of load losses when terminal voltage differences and load voltage losses are equal.


Atslēgas vārdi
load losses, loop-type network, power losses, two-terminal line, voltage loss
Hipersaite
http://alephfiles.rtu.lv/TUA01/000032870_e.pdf#page=190

Survilo, J., Bieļa-Dailidoviča, E. Adverse Currents in Simple Closed Networks. No: Electrical and Control Technologies 2011: Proceedings of the 6th International Conference on Electrical and Control Technologies (ECT-2011), Lietuva, Kaunas, 5.-6. maijs, 2011. Kaunas: Kaunas Univesity of Technology, 2011, 190.-195.lpp. ISSN 1822-5934.