Current Transformer Modeling for Compensating Algorithms
Fourth International Conference on Power Engineering, Energy and Electrical Drives (POWERENG 2013) 2013
Okan Ozgonenel, U. Terzi, Ļubova Petričenko, Romāns Petričenko

This work is about modeling and compensating CT’s secondary current during saturation since working condition of the protection devices such as differential and impedance relays is mostly affected by the operating condition of the CTs. Saturated secondary currents depending on the magnitude of the fault current and remnant flux in magnetic core can cause incorrect operation or operating time delay of protective relays. Therefore, relay experts should take account of the CT saturation problem when they design a protective relay, especially a current differential relay. The objective of this paper is to propose an effective way of CT modeling based on transmission line method (TLM) with Jiles- Atherton technique for correcting secondary current of CT under saturation.


Atslēgas vārdi
TLM; current transmormer; Jiles-Atherton; modeling
DOI
10.1109/PowerEng.2013.6635663
Hipersaite
http://ieeexplore.ieee.org/xpl/articleDetails.jsp?arnumber=6635663

Ozgonenel, O., Terzi, U., Petričenko, Ļ., Petričenko, R. Current Transformer Modeling for Compensating Algorithms. No: Fourth International Conference on Power Engineering, Energy and Electrical Drives (POWERENG 2013), Turcija, Istanbul, 13.-17. maijs, 2013. Piscataway: IEEE, 2013, 522.-527.lpp. ISSN 2155-5516. Pieejams: doi:10.1109/PowerEng.2013.6635663

Publikācijas valoda
English (en)
RTU Zinātniskā bibliotēka.
E-pasts: uzzinas@rtu.lv; Tālr: +371 28399196