Publikācija: Biological Instability in a Chlorinated Drinking Water Distribution Network

Publikācijas veids Zinātniskais raksts, kas indeksēts Web of science un/vai Scopus datu bāzē
Pamatdarbībai piesaistītais finansējums Nav zināms
Aizstāvēšana: ,
Publikācijas valoda English (en)
Nosaukums oriģinālvalodā Biological Instability in a Chlorinated Drinking Water Distribution Network
Pētniecības nozare 2. Inženierzinātnes un tehnoloģijas
Pētniecības apakšnozare 2.1. Būvniecības un transporta inženierzinātnes
Autori Alīna Neščerecka
Jānis Rubulis
Marius Vital
Tālis Juhna
Frederik Hammes
Atslēgas vārdi adenosine tri-phosphate (ATP); biological stability; drinking water; distribution network; chlorine; flow cytometry (FCM); viability
Anotācija The purpose of a drinking water distribution system is to deliver drinking water to the consumer, preferably with the same quality as when it left the treatment plant. In this context, the maintenance of good microbiological quality is often referred to as biological stability, and the addition of sufficient chlorine residuals is regarded as one way to achieve this. The full-scale drinking water distribution system of Riga (Latvia) was investigated with respect to biological stability in chlorinated drinking water. Flow cytometric (FCM) intact cell concentrations, intracellular adenosine tri-phosphate (ATP), heterotrophic plate counts and residual chlorine measurements were performed to evaluate the drinking water quality and stability at 49 sampling points throughout the distribution network. Cell viability methods were compared and the importance of extracellular ATP measurements was examined as well. FCM intact cell concentrations varied from 5×103 cells mL−1 to 4.66×105 cells mL−1 in the network. While this parameter did not exceed 2.1×104 cells mL−1 in the effluent from any water treatment plant, 50% of all the network samples contained more than 1.06×105 cells mL−1. This indisputably demonstrates biological instability in this particular drinking water distribution system, which was ascribed to a loss of disinfectant residuals and concomitant bacterial growth. The study highlights the potential of using cultivation-independent methods for the assessment of chlorinated water samples. In addition, it underlines the complexity of full-scale drinking water distribution systems, and the resulting challenges to establish the causes of biological instability.
DOI: 10.1371/journal.pone.0096354
Hipersaite: http://www.plosone.org/article/info%3Adoi%2F10.1371%2Fjournal.pone.0096354 
Atsauce Neščerecka, A., Rubulis, J., Vital, M., Juhna, T., Hammes, F. Biological Instability in a Chlorinated Drinking Water Distribution Network. PloS ONE, 2014, Vol.9, No.5, e96354.-e96354.lpp. ISSN 1932-6203. Pieejams: doi:10.1371/journal.pone.0096354