Equal Area Criterion and Angle control-based Out-of-Step Protection
2017 IEEE 58th International Scientific Conference on Power and Electrical Engineering of Riga Technical University (RTUCON): Proceedings
2017
Antans Sauļus Sauhats,
Andrejs Utāns,
Edīte Bieļa-Dailidoviča
The article is devoted to wide-area measurements-based out-of-step (OOS) protection system which comprises of several protection terminals exchanging information in real time. Protection system structure and principles of operation described as also operation algorithm presented. OOS regime detection relies on simultaneous implementation of two approaches: generator angles differences are used for multi-swing instability detection while equal area criterion-based (EAC) approach is used for first-swing instability detection. Several deficiencies of EAC-based method, applied to multi-machine environment were revealed by the simulations and the algorithm was proposed to avoid those deficiencies.
Atslēgas vārdi
angular instability, equal area criterion in time domain, out-of-step protection, wide-area protection
DOI
10.1109/RTUCON.2017.8124752
Hipersaite
http://ieeexplore.ieee.org/document/8124752/
Sauhats, A., Utāns, A., Bieļa-Dailidoviča, E. Equal Area Criterion and Angle control-based Out-of-Step Protection. No: 2017 IEEE 58th International Scientific Conference on Power and Electrical Engineering of Riga Technical University (RTUCON): Proceedings, Latvija, Riga, 12.-13. oktobris, 2017. Piscataway: IEEE, 2017, 1.-6.lpp. ISBN 978-1-5386-3847-7. e-ISBN 978-1-5386-3846-0. Pieejams: doi:10.1109/RTUCON.2017.8124752
Publikācijas valoda
English (en)